Raised Access Floor Accessories

Raised access floor accessories are key components that ensure the stability, functionality, and easy maintenance of a raised flooring system. Senmai Floor offers essential accessories including pedestals, stringers, and panel lifters, designed to support reliable installation and long-term performance in offices, data centers, and commercial buildings.

Pedestals act as adjustable supports that allow precise floor height control while providing strong load-bearing capacity. Stringers connect the pedestals to form a stable grid structure, improving rigidity and reducing panel movement. Panel lifters are practical tools that help installers and maintenance staff safely remove floor panels for quick access to underfloor cables and equipment.

With durable materials and precise manufacturing, these accessories help ensure accurate installation, convenient maintenance, and efficient use of underfloor space.

  • Overview
  • Recommended Products

Pedestals

Pedestals serve as the adjustable vertical supports of the system, allowing installers to precisely control floor height while maintaining strong load-bearing capacity and structural stability. 

97.jpg93.jpg95.jpg103.jpg118.jpg108.jpg109.jpg支架斜撑.png

Stringers

Stringers connect the pedestals horizontally, forming a reinforced grid structure that enhances rigidity, reduces panel movement, and improves overall floor alignment.

                                         113.jpg                              114.jpg

Panel Lifter

For daily maintenance and system access, panel lifters enable technicians to safely and easily remove floor panels without damaging the surface finish or surrounding components. 

115.jpg

Get a Free Quote

Our representative will contact you soon.
Email
Mobile
Name
Company Name
Message
0/1000
image

More Faq Us

Frequently Asked Questions?

A raised access floor is a modular flooring system elevated above the structural slab using steel pedestals and stringers, creating an underfloor plenum.
It is widely used in data centers, offices, control rooms, and electrical rooms to support cable management, air circulation, heat dissipation, anti-static protection, and equipment vibration control, while allowing flexible layout changes and convenient maintenance.

Raised access flooring is mainly classified into two categories based on function and application:
•Anti-static raised access floor – designed for data centers, server rooms, and electronic equipment areas
•Network raised access floor – used in office spaces for structured cabling and weak-current systems
Each type can be combined with different surface finishes such as HPL, PVC, ceramic, or carpet.

The height of a raised floor depends on application requirements:
•Office areas: 100–300 mm
•Data centers / equipment rooms: 300–800 mm
•Special projects: Custom heights above 1000 mm available for high-density cabling or airflow requirements

To ensure effective ESD protection, anti-static raised floors must comply with the following:
•Surface resistance: 1 × 10⁶ – 1 × 10¹¹ Ω
•System resistance (panel–pedestal–ground): 1 × 10⁴ – 1 × 10⁹ Ω
These values meet international requirements for protecting sensitive electronic equipment.

For long-term performance and safety:
•Avoid impacts from sharp or heavy objects to prevent surface damage
•Use professional suction lifters when removing panels—never pry forcibly
•Regularly inspect the grounding system to ensure compliance
•Keep underfloor cables organized to avoid excessive load on pedestals
•Replace damaged anti-static finishes promptly to prevent ESD failure

Material & Durability
•HPL: High hardness, excellent wear, scratch, and impact resistance, long service life
•PVC: Softer material, lower wear resistance, more prone to scratches
Anti-static Stability
•HPL: Integrated anti-static layer formed during lamination, stable and long-lasting
•PVC: Surface-coated anti-static layer, performance may degrade over time
Environmental Resistance
•HPL: Resistant to moisture, heat, chemicals, and easy to clean
•PVC: Lower heat and chemical resistance, water exposure may cause edge lifting
Installation & Applications
•HPL: Ideal for data centers and power rooms with long-term fixed layouts
•PVC: Seamless installation option, suitable for areas requiring flexibility or slight subfloor tolerance

Common causes include:
•Improperly installed or uneven pedestals and stringers
•Incomplete contact between pedestal bases and subfloor
•Excessive gaps between floor panels causing friction
Solutions:
•Re-adjust pedestals for vertical alignment and firm fixing
•Add metal shims under pedestal bases
•Replace damaged components and control panel gaps within ≤ 0.5 mm